0.48 hours, and the refrigerant is not in it
Correction code 18205002 at 0.48 hours covers the evaporator TXV on a non-heat-pump Model 3. Mechanically there is very little: disconnect 12V, remove the underhood storage unit, recover the refrigerant, remove the inner HVAC plenum duct, disconnect the 12V positive terminal, unplug the TXV, undo one line fitting nut, remove the mounting bolts, and lift the valve out. Three torque values cover the whole job — 7.2 Nm for the TXV to the HVAC module, 22 Nm for the suction/liquid lines fitting nut, and 6 Nm for the battery positive terminal.
The billing trap is in the header. The 0.48 does not include refrigerant recovery and recharge. A 2025-04-10 revision added a note making you add correction code 18200102 as a separate correction inside the same activity. Quote the job at 0.48 and you have given away a refrigerant service.
Four O-rings, none of them reusable
Four O-rings come off this valve, in two groups:
- Two on the HVAC module, removed after the TXV is off
- Two on the suction/liquid lines fitting
All four are marked remove and discard; all four go back new. This is the line item most often dropped from the estimate, and it is the main reason these jobs come back — reuse an O-ring and the system leaks slowly, and by the time the customer returns there is no evidence of what was fitted.
The order: power down, then refrigerant, then the pipe
- Disconnect 12V power.
- Remove the underhood storage unit.
- Recover the A/C refrigerant. The manual notes that the duct removal steps can be done while the refrigerant is being recovered — two parallel tracks, not a queue.
- Remove the inner HVAC plenum duct, remove the 12V positive terminal cover, loosen the nut and take the positive terminal off the battery to clear access to the TXV.
- Release the clip holding the lines to the harness near the TXV, and disconnect the TXV electrical connector.
- Only after the refrigerant is fully recovered do you undo the fitting nut. Reversed, you are opening a pressurised circuit in the engine bay.
Refitting: module side first, pipe side second
- TXV to HVAC module: 7.2 Nm. That is much lower than most hands expect. It is an aluminium body sealed by O-rings; over-torque distorts the sealing face.
- Fitting nut: 22 Nm, and only once the pipe end is fully seated. Seat it halfway and the nut shears an O-ring as it turns.
Recharge happens concurrently with the remaining steps, not after everything is back together — the manual says so explicitly. That is what lets you find a leak before the underhood storage unit goes back in.
The last step is not assembly, it is a test
Once the charge is complete you must run TEST-SELF_VCFRONT_X_THERMAL-PERFORMANCE, the thermal performance test. Two entry points exist: Service Mode, Thermal, Actions, Test Thermal Performance; or Service Mode Plus, under the drive inverter or drive unit replacement entries, Thermal System Test. Until that routine passes, what you have built is a car that looks assembled.
When the desiccant goes with it
The same circuit has a second correction code: 18202002 at 0.36 hours for the non-heat-pump receiver dryer and desiccant. Its construction is worth knowing, because the desiccant is inside the condenser, not in a service canister on the pipe: remove the cap, depress the inner cap with an 11 mm socket, pull the snap ring, thread an M8 x 1.25 bolt into the inner cap to draw it out, take the desiccant bag out, then pull the filter screen with tool 1145232-00-A and a slide hammer.
The revision history on that page tells you more than the procedure does: 2024-04-02 added a check that the system is not overpressurised before opening the accumulator, 2024-06-12 added a Schrader valve caution, 2024-09-10 added full protective clothing, 2024-09-20 added the separate 18200102 correction code. Three of four revisions are safety. Wear the face shield throughout, and depress both Schrader valves — the manual states plainly that one is not enough and people have been hurt.
The decision is straightforward: if the system has been open to air, replace the desiccant with the valve. If the circuit stayed sealed and only the valve failed, the TXV alone is correct. The two codes add up to 0.84 hours, but the refrigerant service is only charged once.
Four mistakes seen in the bay
| Symptom | Usually this step |
|---|---|
| Slow leak, no visible trace, three months later | O-rings reused, or nut torqued before the pipe was seated |
| Vent temperature never gets low enough | Thermal performance test skipped, valve behaviour never confirmed by the system |
| Estimate short by one operation | 18200102 was not added as a separate correction code |
| Rattle near the underhood storage unit afterwards | Inner plenum duct not fully seated |
When to hand it over
The barrier here is not mechanical, it is refrigerant equipment and diagnostic access: a recovery machine, weighed charging, a leak detector, and a way to run the test routine. Open the circuit without a recovery machine and you vent the charge into the workshop. Skip the routine and you hand the compressor question to the next person. If the equipment is not in the building, do the mechanical swap and sublet the refrigerant work and the test.